Float based gauge system for basic applications. |
 |
|
|
|
 |
Patented microprocessor based digital system
measures fluid level with 1/4" accuracy in
tanks up to 32 feet high. |
 |
System is self powered with 5 year lithium batteries,
allowing stand alone operation with no external power.
|
 |
316 stainless steel sender bar and polyethylene
float resist corrosion, optional PVC sheath for the
sender bar is available for acid applications.
|
 |
LCD display for easy daytime viewing with a back light
for night viewing.
|
 |
System can be factory or field calibrated for any
desired display units, such as barrels, gallons, or
inches of level.
|
 |
High reliability design has no moving parts except for
the float.
|
 |
Built-in overfill warning alarm can activate a horn
or light.
|
 |
Installation and servicing is simplified by modular
design, fibre optic connection between sender bar and
display, no external power requirements, and extensive
diagnostic tools.
|
 |
Operation from -45 to +60 oC ambient
temperature, -45 to +85 oC product
temperature.
|
 |
One year limited warranty.
|
 |
|
|
|
 |
Maximum tank height:
|
25 feet (7.6 m).
|
 |
Principle of operation:
|
Reed switches in sender bar are activated by magnets
in the float, and are read by a microprocessor. Signal
from the sender bar is transmitted to the display
through plastic fibre optic cable.
|
 |
Resolution:
|
1/4 inch (6 mm).
|
 |
Accuracy:
|
+/- 1/8 inch (3 mm).
|
 |
Specific gravity sensitivity:
|
Float sinks one inch (25 mm) in water.
|
 |
Hysteresis:
|
1/16 inch (1.5 mm) (Difference between reading with
float rising and reading with float falling.
Eliminates display flicker.)
|
 |
Maximum fibre optic length:
|
200 feet (60 m). Fibre can be cut with a knife.
|
 |
Ambient temperature range:
|
-45 to +60 oC, product temperature range is
-45 to +85 oC.
|
 |
Battery lifetime:
|
5 continuous operation for sender bar and 10 years on
display. Sender battery can be easily replaced in the
field.
|
 |
Display type:
|
5 digit numerical, 0.50 inch LCD can be programmed to
display level or volume.
|
 |
Display temperature drift:
|
0
|
 |
Alarms:
|
One alarm consisting of a MOSFET transistor conducting
to ground when the alarm is "on". The
transistor has a rating of 1 Amp at 30 volts DC.
Alarm defaults to "off" if the signal from
the sender bar is corrupted or lost. A second,
self resetting alarm output is available for an
overfill warning.
|
 |
Alarm temperature drift:
|
0
|
 |
Power requirements:
|
Display/Sender Bar: None for basic operation.
Display backlight requires 12 volts DC.
|
 |
Display enclosure:
|
Valox enclosure, 4 inches in diameter.
|
 |
Float construction:
|
Cylindrical, approximately 7.25 inches diameter by 4.5
inches high. Float material is polyethylene.
|
 |
Bar construction:
|
One inch diameter 316 stainless steel tube houses reed
switches and temperature sensors. Optional PVC sheath
for bar permits operation in strong acids.
|
 |
Fitting requirements:
|
Sender bar is held in place at the top with a one inch
compression fitting, requires a one inch female NPT
thread in the tank top. At tank bottom either a
weighted anchor or a weld in anchor can be used.
|
 |
Diagnostics:
|
Display shows if signal from sender bar is corrupted
or lost. 916 programmer can measure optical signal
level, sender integrity, display integrity, and can
exercise the alarm points.
|